Asbestos awareness for fire protection trades

Printed Brochure (we have copies of an outdated version of this here)

The guide “Asbestos awareness for fire protection trades” from the Asbestos Safety and Silica Safety and Eradication Agency (ASSEA) provides targeted safety information for fire safety installers and technicians who are at risk of encountering asbestos during inspections, installations, maintenance, and removal of fire protection equipment in older buildings.

Here is a summary of the key points:


1. High-Risk Areas for Fire Protection Trades

Asbestos was commonly used for its fire-retardant properties. Workers in fire protection trades are at risk in both commercial and residential properties built or renovated before 1990.

LocationAsbestos-Containing Material (ACM)
Fire Doors & FirewallsAsbestos-cement sheets or compressed asbestos core used in sandwich construction to provide fire rating. Firewalls often located above dividing walls in ceiling/roof spaces.
Penetrations & RisersAsbestos rope, bagged asbestos, loose-packed asbestos, or sealant used to fill voids between floors, cables, pipes, and ducting to slow the spread of fire and smoke.
Structural BeamsSprayed asbestos or asbestos-containing vermiculite used as fire-rating or acoustic sound-deadening material.
Electrical SystemsAsbestos-based resin board (e.g., Ausbestos or Zelamite) used in main electrical meter boards and fuse boxes.
Surrounding StructureACM in general building materials (walls, ceilings, roof cavities) that must be penetrated to install or inspect equipment.

2. Legal Duties and Safety Requirements

  • Risk & Exposure: Anyone in the fire protection industry is likely to come into contact with asbestos. Even minimal exposure can lead to fatal diseases (mesothelioma, lung cancer) decades later.
  • WHS Laws: Work Health and Safety (WHS) laws apply to all workplaces, including a residential home when a contractor is working there. The Person Conducting a Business or Undertaking (PCBU) has a duty to provide a safe work environment and proper training.
  • Assume and Identify: If a building was built before 1990, always assume that a material is asbestos unless test results from a NATA-accredited laboratory confirm otherwise.
  • Asbestos Register: In commercial buildings, you must ask to see the Asbestos Register before starting work.

3. Mandatory Safe Work Practices

To eliminate or minimise the release of asbestos fibres, tradespeople must adhere to strict controls:

ActionControl Measure
RemovalAlways consider using a licensed asbestos removalist (Class A for friable, Class B for non-friable) if asbestos must be removed or disturbed.
WettingThoroughly wet down the asbestos material and keep it wet during work to minimise dust, ensuring all electrical equipment is de-energised first.
Prohibited ToolsDO NOT use high-speed power tools to cut, grind, sand, or drill asbestos materials.
Prohibited CleaningDO NOT use brooms, compressed air, or high-pressure water to clean asbestos-containing dust.
PPEWear the correct personal protective equipment (PPE), including a P2 cartridge half-face mask, disposable coveralls, and gloves, and ensure a proper fit.
WasteWrap all asbestos waste (offcuts, contaminated rags, PPE) in two layers of 200 µm plastic sheeting or double-bag it, and dispose of it at a designated asbestos-waste disposal facility.